Features

  • Fire spread prevention putty (fire-resistant) for air conditioner piping.
  • Superior in fire spread prevention from wall penetration holes to interior.
  • By expanding 20 times larger by the heat of fire, the gap will be filled up with putty tightly and it prevents from fire intruding.
  • At Japan's Public Testing Institution, test on 1 hour fire-resistant wall was carried out assuming fire intrusion from the outside, and fire spread prevention has been verified.
    *Note: When using this product, please check your country's authorization and standard.


head of this page

Fire-Resistant Performance Test (Example)

*This performance test is an internal evaluation test, which is different from public testing.
Test piece was made on plasterboard as housing wall with pipes and drain hoses penetrated, making heated side to be outside and non-heated side to be inside.
"Fire Spread Prevention Putty TP" is each stuffed in 2 penetration holes and penetration Hole B (Interior) is combined with conventional type putty, "Sealant Putty for A/C AP"(Hole A= TP only, Hole B= TP+AP).
This is a test to verify the change in interior installation by heating after installation.
Air Conditioner Pipe and Accessories
  • Insulated Copper Tube : PC-2420 (6.35x12.70)
  • Insulated Drain Hose : DSH-14
  • Control Cable : VVF-2.0mmx3C
test-image0
Penetration Hole No.Putty
(Outdoor)
Putty
(Indoor)
Shooting Angle
(Inside & Outside)
Identification No.
ATPNoneOutsideA
InsideA'
BTPAPOutsideB
InsideB'
ITEMHeated Side (Outdoor)Non-Heated Side (Indoor)
Before the test
Photo-A1
Photo-A1
[Outdoor]
During installation.
Putty colored in gray is the Fire Spread Prevention Putty TP.
Cover will be set later with Lineset Ducting System "SLIMDUCT SD".

Photo-A2
Photo-A2
[Outdoor]
Test piece is completed.
Cover is set and ready.
Photo-B1
Photo-B1
[Indoor]
During installation.
Addition to TP putty, the right sample (B') is combined together with AP putty.
The left sample (A') is only using TP putty.

Photo-B2
Photo-B2
[Indoor]
Test piece is completed.
During the test Photo-A3
Photo-A3
[Outdoor]
Photo during the heating test.
Insulation, Lineset cover is burnt, but both A, B penetration holes are sealed with Fire Spread Prevention Putty TP.
After the test
Photo-A4
Photo-A4

Photo-A5
Photo-A5
[Outdoor]
After heating.
From intense heating, outside wall is cracked.
Red flame is burning, but this is caused by wood shaft burning inside the test piece.
Photo-B4
Photo-B4

Photo-B5
Photo-B5
[Indoor]
After heating.
By covering with Fire Spread Prevention Putty TP, it prevented fire from entering penetration hole A' & B'.
Since penetration hole B' (right) is combined with AP putty, smoke inflow is small.


head of this page

Lineup

TP - FIRE SPREAD PREVENTION PUTTY -

Code No.Item No.ContentsPcs/Pkg
06040 TP-160 160g 60


head of this page

Specification

Color Gray
Material Polybutene-line Resin
Characteristic Non-drying (Non-hardening)
Specific Gravity 1.8 (Typical Value)
Temperature Range -20℃ to 50℃
Working Temperature 5℃ to 40℃


head of this page

Caution

  • Fill in 1 hole (under Ø70mm) with whole putty (160g) from the outside.
  • To prevent putty from deteriorating and rain intruding from the hole, please be sure to be covered with Wall Inlet of our SLIMDUCT SD series or equivalent.